One power feed, several chargers. With power daisy chaining, the supply runs from one Peblar Dual to the next, so you do not need a separate cable from the distribution cabinet to each charger. This article explains what power daisy chaining is, what you need, how to build the installation and which limits apply.
What is power daisy chaining?
With the Peblar Dual, power can be daisy chained from one charger to the next charger. Just install the Peblar Dual Daisy Chain inside the Dual charger and directly connect the incoming and outgoing power cable.
This allows multiple chargers to share the same power feed instead of running individual cables back to the distribution cabinet for each charger.
The benefit is simple: less cabling, a smaller distribution cabinet and less installation work.
So while you see more charging sockets, behind the scenes you need less infrastructure.
More sockets. Less infrastructure.
What do you need to power daisy chain the Peblar Dual?
Required accessories:
Daisy chaining the power cabling of the Dual requires the Peblar Dual Daisy Chain:
| Product description | Peblar article number | EAN/GTIN |
|---|---|---|
| Peblar Dual Daisy Chain | 6004-2601-5800 | 8721008599458 |
The Daisy Chain block can be installed inside the Peblar Dual Back and allows you to directly connect the incoming and outgoing power cable within the Dual charger.
Note that when you use the Peblar Dual Daisy Chain, you can only use bottom cable entry: there is not enough room in the Peblar Dual Back to have both cables enter from above (see installation manual).
The Peblar Dual Daisy Chain provides a mains input and output connection and accepts cables up to 16 mm², with a maximum current of 80 A. The daisy chain accessory box contains an extra grommet for the outgoing power cable and the required screws for installation.
How do you build a power daisy chain installation with Peblar Dual?
Peblar Dual supports power daisy chaining, allowing multiple chargers to be connected through a single mains supply path rather than wiring each charger individually from the switchboard.
A typical daisy chain configuration:
In the configuration shown above:
a) Built-in protection within each Peblar Dual
Each Peblar Dual has an integrated 40 A overcurrent protection device (C40), providing overload and short-circuit protection for both the connection points and the charger itself.
b) Upstream protection
The upstream overcurrent protection provides overload and short circuit protection to the cable run up to the charger. The maximum allowed value of the upstream overload protection is 100 A. Using the Peblar Dual Daisy Chain limits the maximum value of the overload protection to 80 A. The example in the diagram shows B80 overload protection.
The example shown uses an 80 A upstream overload protection (B80) and 16 mm² cabling for the daisy chain cabling.
Note that an upstream RCD might be required depending on earthing system, earth fault loop impedance and local regulations.
Cable sizing and the required upstream protection must be determined by the installer for the specific installation.
How to set it up
Connect the mains supply from the distribution board to the Daisy Chain block in the first Peblar Dual. From the same Daisy Chain block, run a mains cable to the next Peblar Dual. Repeat this connection for each additional charger in the chain.
The Peblar Dual Daisy Chain block (article 6004-2601-5800) provides connections for the incoming and outgoing mains cables.
See the Dual installation manual for installation instructions: Where can I find the Peblar Dual installation manual?
Related questions
- Can I use SWA cable (steel wire armoured) for daisy chaining the Peblar Dual?
- Can a single charger be used at the end of a Peblar Dual power daisy chain?
- What if I need more than 16 mm² cable for a Peblar Dual daisy chain?
- What is the maximum number of Peblar Dual chargers in a power daisy chain?
- Why choose a B class protection in the main distribution board for a daisy chain?